GC: An eyelet from an inlet was located at the bottom of the pool. Operator put back and secured it to the proper inlet. Be sure to watch for inlets having eyelets for duration of the season.
0.0
15.
Ring buoy was dry rotted. Ring buoy shall be in good condition. CDI Operator replaced with new ring buoy.
chlorine level less than 1.0 ppm chlorine must be maintained at least at 1.0 ppm at all times.
6.0
3.
ph greater than 7.8. ph must be maintained between 7.2 and 7.8.
6.0
5.
daily records are not being kept on some days. there are not any weekly total alkalinity and cyanuric acid readings recorded. 30 days to keep accurate daily and weekly recordings.
4.0
12.
vaccuum line cover is missing. replace vaccuum line cover within 30 days of this inspection. fittings must be in place and in good repair.
4.0
16.
Fensing is not in compliance with current code but does meet compliance of applicable code for the year the fence was constructed.
4.0
17.
clear deck spacing of 6' is required. furniture obstructed deck space. move furniture to all for 6' of deck spacing within 30 days of this inspection.
Fensing is not in compliance with current code but does meet compliance of applicable code for the year the fence was constructed.
4.0
18.
Warning sign with "children should not use the swimming pool without adult supervison" "adults should not swim alone" was not posted. Sign had fallen down behind the trash can. repost warning sign. 30 days has expired. CPO corrected at inspection by hanging a new pool rules sign.
4.0
19.
Signs prohibiting glass and pets is missing. corrected at inspection by handing of a new pool rules sign.
4.0
24.
Flow meter was not operable repair/replace flow meter to allow field verification of GPM. 30 days has expired. CPO repaired flow meter during inspection.
4.0
General Comments
17. 6' of clear deck space is required. pool chairs encroaching on deck space required.
all violations except 16. were corrected by CPO at inspection. Intent lifted.
Warning sign with "children should not use the swimming pool without adult supervison" "adults should not swim alone" was not posted. Sign had fallen down behind the trash can. repost warning sign. 30 days to correct.
4.0
24.
Flow meter was not operable repair/replace flow meter to allow field verification of GPM. 30 days to correct.
4.0
General Comments
17. 6' of clear deck spacing is needed. Pool chairs had been moved and were closer than 6' encroaching on deck space. 30 day intent issued.
ring buoy rope had dry rotted and was frayed. ring buoy rope was replaced at inspection and cut to 37'.
6.0
16.
Fence is not compliant with .2528 (a). Fence should be at least 48' in height, 45' between horizontal members, no more then 4' between vertical members. Due to date of fence construction which was before 2010, it is not mandated to repair to meet .2528 (a), it is recommended.
4.0
General Comments
7. cleaning is needed of the tiles at the water line. pollen/debris build up. 12 one return inlet is missing the directional component. replace this piece to maintain the inlet in good repair. no night swimming.
Fence is not compliant with .2528 (a). Fence should be at least 48' in height, 45' between horizontal members, no more then 4' between vertical members. Due to date of fence construction which was before 2010, it is not mandated to repair to meet .2528 (a), it is recommended.
4.0
17.
Chairs on pool deck are too close to the pool. Should have a minimum of 6' of clear deck space around pool. Chairs moved. CDI
4.0
General Comments
*Operator must be consistent in recording the weekly cyanuric acid levels and total alkalinity.
Fence is not compliant with .2528 (a). Fence should be at least 48" in height, 45" between horizontal members, no more then 4" between vertical members.
4.0
17.
Should have a minimum of 6' of clear deck space around pool-chairs are too close to pool.
4.0
22.
There was not an emergency phone available at start of inspection. Phone was brought during the inspection and connected with 911. A permanent landline phone that is capable of connecting with 911 must always be available.
6.0
24.
Flow meter was not operating at start-operator repaired. Monitor.
4.0
General Comments
Water is clear and main drains are visible. Water has a green color and is brown at fill line, in restrooms, and tap on bldg. Neighbor stated that the water does that occasionally. Monitor clarity to make sure it is not effected.
Ring buoy rope was 40 feet long. Should be 37.5. I retied rope to 37.5.
6.0
General Comments
*Have two warning signs that are in compliance. 1 sign is faded and not in compliance *Phone had static which made it hard to hear 911. Monitor and if gets worse will need to make adjustments.
There is excess rope on ring buoy. Rope should only be 1.5 times the width of the pool. Too much rope can cause the rope to be tangled up. Cut excess rope. Currently excess rope is wrapped around ring buoy.
Monitor mulch movement on the backside of fence. Must have a minimum of 48" between bottom/ground and fence height with no more then 4" between ground and bottom of fence.
From the outside of fence to pool, the fence should be 48" in height. Suggest installing a taller fence that meets this requirement or removing excess wood chips in landscaping.
4.0
17.
On the far right side of pool, chairs are closer then the 6' space requirement. Should keep a minimum of 6' clear deck space around pool. chairs moved-CDI
NO DIVING markers are faded and need to be repainted or replaced with 6"x6" tiles. Depth marker on pool wall/fence is missing on right side of pool next to stairs. Markers cannot be spaced more than 25' apart.
4.0
15.
Rope on ring buoy is in poor repair and fraying apart. Immediate
6.0
21.
One light fixture is half filled with water and the small light fixture is loose in wall and coming out.
NO DIVING markers are too faded! Can hardly see them. Repaint or NO Diving tiles. DO NOT use marker (sharpies,etc.) Correct as quickly as possible but not longer than 30 days. Or permit will be suspended. Intent issued.
4.0
15.
Throw rope was not attached to ring buoy. Was reattached. Monitor daily. CDI
6.0
27.
If water is going to be standing in bottom of backwash pit. Pipe from filters must be replumbed. There must be an air gap so the discharge pipe is above the water level.
Equalizer lines in skimmers were blocked at start of inspection-plugs removed and compliant covers installed on pool wall.
4.0
9.
Greater than 25 feet between "NO DIVING" markings on pool deck in 1 area. Signs temporarily installed on deck at pool edge until one can be painted on.
4.0
15.
Ring buoy rope not in good repair, replace with one in good repair. Repaired.
6.0
25.
Make sure breaker stays on for the ventilation in pump and chemical room.
0.0
29.
Repair the loose baseboard in restrooms.
0.0
General Comments
Water way equalizer covers installed. Drain covers secure, Pump 3 Hp