two weirs were still missing after 30 day intent issued. skimmers must be in good repair with weirs in place. replaced at inspection.
4.0
9.
Depth markers and "no diving" letters/numerals were less than 4" as noted in last inspection to be corrected within 30 days. were not corrected in that time frame. repaired to 4"at inspection.
4.0
16.
Back egress gate is still not self latching as noted in the last inspection to be corrected within 30 days from that inspection. Gates must self close and self latch. gate repaired at inspection. verified to self close/self latch.
Chlorine reading less than 1 ppm. Chlorine must be maintained at least 1 ppm. Raised to greater than 1 by cpo at inspection.
6.0
5.
Weekly total alkalinity and cyanuric acid readings are required. Weekly readings are not in CPO book.
4.0
7.
Black and green algae present. Walls and floors should be clean. Remove algae within 30 days for this inspection.
4.0
8.
Replace all missing weirs. Skimmers must be in good repair with weirs in place. 30 days to repair.
4.0
9.
No diving and depth makers letters less than 4” modify/ extend letters to 4” required heights within 30 days.
4.0
16.
Back emergency egress gate is not self closing from all distances of opening. Repair gate withing 30 days all gates must self close and self latch from all distances.
"NO diving" and depth marker letter/number height is slightly less than 4". letters were previously modified to 4" but had faded. Letter extension were made to correct letter/numbers to 4" required letter/number height. monitor through the season and make repairs as needed.