At start of inspection free chlorine level was 0ppm. Free chlorine level shall be at least 1ppm. CDI operator was able to raise free chlorine level to at least 1ppm.
6.0
8.
Weirs were missing from all skimmers. All surface skimmers shall be in good repair. CDI operator was able to replace weirs.
4.0
16.
Places under the fence at the gate were more than 2" from the ground. Fences shall be no more than 2" from bottom of fence to ground. CDI mulch was added where it had be previously washed out. Continue to monitor through season.
4.0
24.
Flow meter is located on pipe that is before the filter. Flow meter should be able to indicate the rate of flow and should be installed on the piping after the filter.
4.0
25.
Chemicals should be stored in the chemical storage room. They are currently being stored in the pump room.
2.0
General Comments
The only operational gate is the front one by the building. Gate from front parking lot is locked.
Erosion feeder is the only operational disinfectant system that is installed. Liquid feeder was not powered/operating.
Flow meter is located on pipe that is before the filter. Flow meter should be able to indicate the rate of flow and should be installed on the piping after the filter.
4.0
25.
Chemicals should be stored in the chemical storage room. They are currently being stored in the pump room.
2.0
General Comments
The only operational gate is the one by the building-Gate from front parking lot/hill is locked.
Erosion feeder is the only operational disinfectant system that is installed. Liquid feeder was not powered or operating.
Chlorine at arrival was too low. chlorine shall be at least 1ppm, operator was able to fix.
6.0
3.
PH at arrival was too low, PH shall be between 7.2 and 7.8. Operator was able to fix.
6.0
24.
Flow meter is located on pipe that is before the filter and it was not operational. Flow meter should be able to indicate the rate of flow and should be installed on the piping that is after the filter. Operator repaired meter so it is operating and indicating the rate of flow.
4.0
25.
Chemicals are stored in the pump room. Should be stored in a separate locked storage room.
2.0
General Comments
GC: Equalizer lines have been plastered over pool wall. The line below the skimmer basket must be emptied and plugged by next season.
Equalizer lines have been plastered over on pool wall. The line below skimmer basket must be emptied and plugged.
0.0
16.
Fence has over 2" between ground and bottom of the fence, and more then 4" between the vertical members. Fence should not have more than 2" between the ground and bottom of fence and should not have anymore than 4" between the veritcal members. Fence constructed prior to 2o1o so it is strongly recommended to comply with .2528 (a).
4.0
24.
Flow meter is located on pipe that is before the filter and it was not operational. Flow meter should be able to indicate the rate of flow and should be installed on the piping that is after the filter. Operator repaired meter so it is operating and indicating the rate of flow.
4.0
25.
Chemicals are stored in the pump room. Should be stored in a separate locked storage room.
2.0
General Comments
Seasonal Permit Issued
The only operational gate is the one by building. Other gate by steps is locked.
small area of plaster has popped up from pool floor. patch was applied to this area to smooth out the area. pool walls and floors must be in good repair.
4.0
17.
small area round the skimmer at far end with greater than 1/2" offset area was puttied and smoothed at inspection eliminate trip hazard.
4.0
25.
Store chemicals in a separate room from pump room.
2.0
General Comments
No night swimming back gate was locked at inspection and not evaluated. must remain locked at all times.
There are several areas below the fence that is over 4" between the fence bottom and grade. Fill in areas greater than 4 inches. Fence constructed prior to 2010.
4.0
25.
Chemicals should be in separate room from pump room.
There are several areas below the fence that there is over 4" between the fence bottom and ground. landscape company on premises removing trees. Suggest filling in areas >4"
4.0
23.
pressure switch for the liquid chlorine feeder was not operational, therefor the feeder could not be and turn off if pump is off. Operator was able to remove the liquid chlorine system. Install an erosion chlorine feeder.
4.0
24.
Flow meter is on the pipe coming from pump should be on the return piping.
4.0
25.
Chemicals are in the pump room for storage. chemicals should be stored in a separate locked storage room.
2.0
General Comments
permit issued. pool cannot open to bathers until all executive orders concerning Covid-19 are expired and not extended. only operational gate is gate by the building.
The cover to the vacuum port on pool wall has been torn off. Vacuum port must have self closing cover or plugged when not in use. Operator was able to plug -CDI
4.0
15.
Rope on the ring buoy was cut into 3 different pieces then tied back on buoy in 3 different spots. There must be a single rope that is 1 1/2 times the width of the pool and securely attached to buoy. Operator was able to supply a new rope at 1 1/2 times width of pool and attach. CDI
6.0
24.
Flow meter should be installed on the filtered water piping - not the pre-filter piping.
4.0
25.
Chemicals should be stored in a separate locked storage room w/ lighting and ventilation.
2.0
General Comments
-The WARNING NO LIFEGUARD OF DUTY sign in pool fence is fading-monitor and replace when unable to clearly read letters.
Leaves on bottom of pool and build up on stairs. Operator in process of removing and cleaning. CDI. When open to the public, pool must stay in a clean maintained state.
4.0
18.
The "WARNING" on the Lifeguard sign is starting to fade. Re-color when needed.
0.0
25.
Chemicals should be stored in a separate locked storage room w/ lighting and ventilation.
The section of deck where coping meets deck at 4' section - the gap is over 1/2". Employee was able to fill in gap with epoxy bond to slope concrete to coping.
4.0
24.
Flow meter is new this year and not capable of measuring the flow of pool circulation. Install a flow meter that is capable of measuring flow.
4.0
25.
Chemicals should be stored in a separate locked storage room from the pump room.
2.0
General Comments
Permit not issued-pool must remain closed until reinspected.
Vacuum line open and not covered on pool wall. Unless in use, this must be capped.
4.0
16.
Gate does not self latch when opened to certain distances. Magna latch installed on gate so not it is self closing and self latching from all distances.
4.0
General Comments
There are several small freshwater leaks in the female restroom that should be repaired.
There is one area on the pool wall (by ladder at 5' section) that paint is cracked and chipping. Monitor to make sure this does not spread.
4.0
15.
Ring buoy had several tears in the cover. Unit was replaced with a new one w/a 30 foot rope.
6.0
24.
Provide an extra strainer basket.
4.0
25.
Chemicals should be stored in a separate storage room. Fan not operational, however with the 2 cutouts (in door and wall above door), this allows for natural ventilation.
No diving and depth markers msut be separated by no more than 25'. New tiles were put down and in one area they were too far apart. Repaired by painting on additional markers.
Must have 6 feet of clear walkway around pool on deck. Move chairs to allow for the required 6 feet and 5 feet around handrails.
4.0
24.
Flow meter stuck, repaired. Make sure meter stays in operation.
4.0
25.
Motor on ventilation system in chemical room not operating. Covers were removed to allow a natiral flow between top and bottom openings in room.
2.0
28.
Provide a sign instructing bathers to shower before entering pool.
2.0
General Comments
-Letter from Hines Engineering stating compliance with the VGB Act received and approved. -Skimmers have approved covers according to the above referenced letter. -Night swimming not listed on application-close pool at 8:00 as stated.