Fence does not meet the current fencing code with areas greater then 2" below fence but less than 4". fence is in compliance for the year of fence construction.
Fence does not meet the current fencing code with areas greater then 2" below fence but less than 4". fence is in compliance for the year of fence construction.
4.0
General Comments
pool was painted iwth instil royal blue paint. data sheet for paint has 57% reflectance.
Fence does not meet the current fencing code with areas greater then 2" below fence and the ground. Should have 45" between the horizontal members on fence. Fence constructed prior to 2010, recommend complying with .2528 (a)
4.0
17.
Should have 6' of clear walkway around the pool on deck. Table and chairs in deck space. Moved. CDI
ring buoy throw rope had dry rotted and was in bad repair. throw rope was replaced at inspection to a length of 27'. maintain in good repair.
6.0
16.
magna latch device was at 53"above grade. moved to 54" at inspection. monitor for settling. locking mechanism must be at 54" above grade. door to meeting room was sticking and not self closing. adjusted at inspection to self close. fencing does not meet current fencing code with areas greater than 2" below fence but less than 4". Fence is in compliance for the year of fence constuction.
4.0
General Comments
Pool was painted with Inslx royal blue paint. according to date sheet paint has 57% reflectance. Data sheet included in file.
One of the tiles from the color band on the edge of steps was missing. Operator was able to place epoxy in the area to make a solid band on the step. CDI
2.0
17.
metric depth marker was missing causing an offset > 1/2 inch. Operator filled with a plexi glass tile with epoxy beads on it to make slip resistant. New tile ordered. CDI
4.0
General Comments
*Monitor the ring buoy and replace when worn. *Monitor the gate to make sure it is self closing and self latching from all distances.
Distance under fencing is greater than 2 inches to grade. Fence meets requirements for the year of construction. Gate was snagging on something and not closing fully. This was addressed during inspection and was closing. CDI
4.0
17.
Some areas did not have 6ft of clear deck space around pool due to furniture. Furniture moved to clear 6ft during inspection. CDI
4.0
General Comments
One tile is missing on the color band at steps. Replace tile.
Distance under fencing is greater than 2"from grade. fence is in compliance for the year of construction.
4.0
General Comments
13. ONe tile is missing on the color band on the top step. Replace/paint this section. 23. hand feeding chemicals to the pool is not an approved chlorination method.
Gate did not self-latch from all opening at start of inspection. CPO cam out to repair gate. Gate was self-closing and latching at all point at the end of inspection.
Fencing does not meet current fencing rules. Fence was constructed prior to 2010 and is in compliance with applicable fencing rules for that yr per rules .2528(B)
4.0
25.
Keep chemicals in separated locked room from pump room.
2.0
29.
Hot water in excess of 110F in bathrooms. Hot water must be less than 110F.
Door to meeting room that opens onto pool deck was not self latching. Door repaired at inspection. Monitor this door. Fencing does not meet current fencing rules. Fence was constructed prior to 2010 and is in compliance with applicable fencing rules for that year per rule . 2528 B
4.0
29.
Hot water in excess of 110F in bathrooms. Hot water must be less than 110F.
2.0
General Comments
5. Check and record total alkalinity and cyanuric acid levels weekly. 25. one bucket of chlorinator sticks stored in the pump room. Was taken to separate chemical storage room. Keep chemicals out of equipment room. No Night Swimming.
Water is cloudy with greenish tint. Main drains could not be clearly seen to be inspected. Pool permit immediately suspended. Call 919-989-5180 when pool is clear.
6.0
16.
Pool fence does not meet new fence requirements, but is allowed to operate.
Pool records were reviewed and were filed on site for greater than the required 6 months. Records had the required daily records, however, no weekly records of total alkalinity and cyanuric acid levels are required.
4.0
9.
No Diving marker was found loose on the deck. Pool management was notified and reattached the tile.
4.0
16.
Gate was greater than 2 inches from the ground in an area. Pool management was notified and corrected this. The gate was also found to be less than 48 inches tall in one area. This was also corrected by pool management. Fencing is out of compliance with 15ANCAC 18A.2528(A)(1)-(4) however, the pool was constructed in 2008, therefore, in compliance according to 15ANCAC 18A.2528(c). *Recommend bring fence into compliance with 15A NCAC 18A.2528(A)Fencing
4.0
17.
An area around the step-handrail was missing concrete. Pool management was notified and repaired the area. The deck was pressure washed today prior to inspection causing this and the loose tile.
4.0
29.
Hot was greater than 110F (approx. 116F). Hot water should be no more than 110F.
The No Diving tile at entrance of pool deck on left was not attached to deck. Intent issued to permanently attach to pool deck- glue was used to reattach under current conditions but it needs to be cemented down.
4.0
10.
Floats on safety rope cannot be spaced anymore than 5 feet apart.
2.0
24.
Flow meter not operational. Intent issued to repair.
pH of pool water is 7.0 or less. Must be in a range of 7.2-7.8
6.0
10.
Floats on a safety rope were spaced more than 5 feet apart. Adjust floats on rope.
2.0
24.
Circulation system was under repair and not on while bathers were in pool. Pool needs to be closed if the circulation system has to be turned off for any reason.
4.0
General Comments
Water level was just above the equalizer lines and hose in pool to fill. Finish filling pool, balance water chemistry and have the circulation system operating. Pool closed/Permit suspended.
Floats on the safety rope more than 5 feet apart. Floats were adjusted. There cannot be more than 5 feet between the floats on safety rope.
2.0
15.
Rope on the ring bouy was ~20 feet long. Rope should be 50 feet or 1 1/2 times width of pool (use the smaller of two). Rope should be 27 feet (1 1/2 times width of pool). Rope replaced.
6.0
16.
Gate to pool is not self latching at start of inspection.
4.0
17.
Must have 5 feet of clear walkway around pool deck-chairs are obstructing the 5 feet.
4.0
24.
Flow meter is not operating. Must have a properly operating flow meter to check flow in circulation system.
Free chlorine level at the initial reading was 0.5 ppm. Must be at least 1.0 ppm in free chlorine available level. Chlorine solutions added to non provide 20 ppm.