Ring buoy rope was 60' long. The ring buoy rope must be 1/5 times wider than the width of pool or 50feet the lesser of the two. Rope was tide into coil to make 50 feet long. CDI
Total alkalinity and cyanuric acid levels are not being checked weekly. Written records should include weekly total alkalinity and cyanuric acid levels.
Keep daily written records of main drain checks and weekly total alkalinity levels.
4.0
22.
Emergency telephone was not operating- no dial tone or connection. New phone installed in the emergency phone box which was able to connect to 911. CDI
6.0
General Comments
**Pool heater not on during inspection-when on, pool water cannot be heated to >90F.
The rope that attaches to the outside of ring buoy was trapped behind the holder that was zip tied to the fence-this made the ring buoy unable to be moved or used in the case of an emergency. Scissors were used to cut zip ties and ring buoy is not able to be accessible. Always hand/place in a spot where it is accessible.
6.0
25.
Doors to both the pump room and chemical storage room were unlocked which makes them accessible to anyone. Both must be kept locked when not in use by operator/owner.
The pH of the pool water was >8.0 at start of the inspection. Acid added and now a 7.4. Must maintain a pH between 7.2-7.8.
6.0
4.
Water heater for pool not on during inspection. When on, water cannot be any warmer then 90F.
0.0
5.
Keep daily free chlorine levels, daily pH levels and daily temperature of pool water. Keep weekly total alkalinity levels, and weekly cyanuric acid levels. Keep daily main drain checks.
0.0
General Comments
Rope on ring buoy cut to 50 feet.
Gate by the pump room opens into the pool deck-letter from fire marshal received stating this is an egress from building and must open away from building.