2 inlets were missing covers and one vacuum port was. Inlets and vacuum ports must be in good repair. Operator fixed during inspection.
4.0
17.
Areas of the pool deck around the pool have less than 5 feet of clear spacing due to HVAC vents. Pool should have 5 feet of clear deck way around the pool.
4.0
22.
Emergency phone not working properly. There must be an emergency phone available on the pool deck or within 75'! Sign placed on Emergency phone to use front desk phone. Front desk phone operational.
Areas of the pool deck around the pool have less than 5 feet of clear spacing due to HVAC vents. Pool should have 5 feet of clear deck way around the pool.
4.0
24.
Flow meter was not providing an accurate reading of the circulation GPM flow. Operator was able to repair and now providing the GPM as engineered to flow. CDI
4.0
29.
Hot water in the restrooms was ~113F. Hot water should not be any warmer then 110F.
2.0
General Comments
Year Round Permit Issued
-Skimmer grate on far side by diving platform has a slight crack-monitor and replace when needed. -Wall depth marker was blocked by a storage unit-unit moved. Do not block.
The main drain on far side of pool is broken and damaged. The pool is closed until main drain can be replaced.
6.0
9.
Depth marker on wall faded (4 1/2 ft) and several are blocked by chairs/bench.
4.0
11.
If diving platforms are up they must have something on them covering or restricting use by the general public.
2.0
15.
Pool has 2 ring buoys both missing the 50 foot rope. Pool is >3000sq ft which requires 2 units of life saving devices- only 1 body hook on pole was available.
6.0
17.
Parts of the skimmer grate on pool deck is cracked or missing -replace.
4.0
24.
Flow meter is not operating -repair.
4.0
General Comments
Pool is closed until #6 and #15 are repaired and reinspected by the Health Department.
(4 1/2 FT) Depth marker on wall faded-replace. Make sure all depth markers are visible.
4.0
11.
Ladder on far side of deep end is loose-repair. When diving platforms are up they must have something on them covering or restricting use by the general public
2.0
17.
Several areas of the gutter grate are damaged and need to be replaced.
4.0
29.
Hot water in the restrooms was >120F. Should not be any warmer then 110F.
2.0
General Comments
Main drain that was cracked has been replaced with a new drain cover and safety equipment is compliant. Pool is now approved to reopen to bathers.
One screw was missing on the main drain but was secure. Operator replaced missing screw. Always check to make sure main drain is secure. CDI
6.0
11.
One step ladder was slightly loose. Make sure ladders are tightly secure. CDI Operator secured the ladder.
2.0
17.
There should be 5 feet of walkway around pool deck. HVAC system is obstructing walkway. There are a couple of small tiles loose on the deck. They do not create a trip hazard but should be secured. Decks should be structurally sound. Tiles were shown to operator to secure. CDI operator is caulking tiles.
4.0
29.
Hot waster in bathroom was greater than 110 degrees F. Water should be at 110 degrees F or below for the bathroom.
2.0
General Comments
Emergency phone is now working with the correct address in the pool area. Permit issued.
There should be 5 feet of walkway around pool deck -HVAC system is obstructing walkway.
4.0
22.
Emergency telephone connects w/ 911, the 911 call center gives the address of 215 versus 205. For this reason, the emergency phone on pool deck cannot be used. About 15 feet from pool entrance there is a phone at the front desk that when used to call 911, they have the correct address. This phone is now designated the emergency phone. Sign placed on phone box stating emergency phone at front desk. Large sign posted at front desk phone stating dialing instructions, address and phone number.
6.0
28.
Shower signs not posted. Always have a sign instructing bathers to shower before entering pool - repaired.
2.0
29.
Hot water in the restrooms is >110F. Should not be any warmer then 110F.
2.0
General Comments
It is recommended to have all electrical components of all pools inspected by a licensed electrician. Submit report if completed to our office.
Pool floor is deteriorating and is beginning to hold dirt/debris. Will need to be repaired in near future.
4.0
15.
Ring buoy ropes were in poor repair and easily breakable. Ropes were replaced.
6.0
16.
Door to restrooms are not latching properly. Repair by 3.19.14!
4.0
17.
Repair broken plastic grates as needed on deck around pool.
0.0
22.
Phone on pool deck is not working properly. Sign is placed on call box to direct emergency to phone at front desk as a temporary solution. Front desk is 25' from entrance to pool deck.
Keep watch on the grates around pool deck to make sure they stay in good repair.
0.0
15.
Ring buoys had a tear in cover. Buoys must be in good repair-Both were replaced.
6.0
28.
No shower sign was posted at start of inspection-repaired.
2.0
General Comments
** Support beams are very rusty and starting to chip at base- rust is leaching onto walls and floor. All damaged areas on beams will need to be replaced soon**Remove rusty spots on walls and floors. ***
Ring buoy ropes were to long. Must be 50 ft long or 1 1/2 times the width of the pool. The indoor pool rope must be 50 ft long. Rope cut to preps length.
0.0
16.
All doors must self close and latch that are in use to prevent children from entering. All Other doors can be locked shut to prevent child access. Corrected by end of inspections.