Timer on the spa is allowing it to go over a 15 minute time frame. The spa timer must cut off after 15 minutes maximum. Intent issued to repair.
4.0
29.
The hot water in the restroom was >120F. Should not be any warmer than 110F
2.0
General Comments
Door to the pool deck must be self closing per .2528 (a)(8) but do not have to be self latching. If propped open then there must be lifeguards on duty for each body of water. *door attendant is always on duty*
The acid feeder does not stop feeding acid when the motor to the circulation system is turned off, it continues to feed.
4.0
29.
The hot water in the restroom was >120F. Should not be any warmer then 110F.
2.0
General Comments
Motor has been replaced since the last inspection by an electrician. The motor replacement and bonding has not been signed off by building inspections. Contact them for a permit and inspection. Once they pass and sign off, then contact for a reinspection for permitting. Pool permit suspended - pool/spa closed sign posted. Have staff monitor to make sure no one enters or uses the spa!
Spa timer is allowing the jets to run for a time period over 15 minutes (spa timed 2 different times). Repair by 12-8-19 so the jets cut off at 15 minutes maximum.
4.0
29.
Hot water in the restrooms was ~120F. Should not be any warmer then 110F.
2.0
General Comments
Color band on steps and bench is now >2" and is in the approved location on step. Intent that was issued to repair this is lifted.
Intent Issued to repair the spa timer. At front entrance-front door latch malfunctioning-repair.
Spa has a timer for lower jets and a timer for the upper jets. The timer for the upper jets is not cutting off at the 15 minute time limit. The switch to the upper jets is blocked so it cannot be turned on or used. Repair switch so it does not allow the jets to run past 15 minutes. CDI
4.0
24.
Flow meter was not operational at start of inspection- Meter was cleaned and now properly operating. CDI
4.0
29.
Hot water in the restrooms was 118F. The maximum water temperature should not be any warmer than 110F
The pH at start of inspection was less than a 7.0. Soda ash added to bring the pH to a 7.2. Must stay in a range of 7.2-7.8.
6.0
14.
The main spa timer was allowing the jets to run longer than 15 minutes. The second jet timer was allowed to run and it ran under 15 minutes. The main timer was disabled from use.
4.0
29.
Hot water in the restrooms was 122F. Should not be any warmer than 110F.
The pH of pool water was a 7.0 at start of inspection. The pH was increased and now a 7.4. Must stay between 7.7-7.8.
6.0
23.
The automatic acid feeders continued to pump when the circulation system was turned off. When the circulation system is off, the feeders must also automatically turn off. Ecolab repaired during inspection. -monitor.
4.0
29.
The hot water in restrooms was 121F. Should not be any warmer than 110F.
Flow meter to spa was stuck and repaired during inspection.
4.0
29.
Hot water in shower and restrooms were at 135*F, does not need to exceed 110*F.
2.0
General Comments
Main drains were replaced: wall/step - Afra #1164 expires 5 years, floor - paramount SDX Retro expires 5 years. Spa jet timer was 13:51 minutes. Permit is being issued to spa.
Equalizer lines in the skimmers have been plugged. VGB compliant equalizer covers that are properly sized to handle the gpm flow must be installed by April 1st, and lines unplugged.
4.0
29.
Hot water in the restrooms at the lavatories way too hot. Should be a maximum of 110F.
2.0
General Comments
Will return on April 1, 2011 to verify compliance with the equalizer covers in order to remain in operation.