The fence has areas that has >4' between vertical members and 2' between the bottom of the fence and the ground. Due to the fence being installed prior to 2010, it is recommended to meet the current code of no more than 4' between vertical members and no more than 2' between the bottom of the fence and ground.
4.0
17.
There should be 6' of clear walkway around the pool on deck- chairs are blocking the 6' clearance
4.0
25.
Large container of liquid chlorine is stored in the pump room. Should be stored in the chemical storage room
2.0
General Comments
5' depth tile marker now secure to the pool deck-Intent to Suspend is lifted.
The deck tile depth marker in the 5 FT deep section was facing the wrong way and not secure to the deck. It must be secured-Repair.
4.0
16.
The fence has areas that has >4' between vertical members and 2' between the bottom of the fence and the ground. Due to the fence being installed prior to 2010, it is recommended to meet the current code of no more than 4' between vertical members and no more than 2' between the bottom of the fence and ground.
4.0
17.
There should be 6' of clear walkway around the pool on deck- chairs are blocking the 6' clearance.
4.0
22.
Emergency telephone was not operating at start of inspection. Community member brought a phone that operates and the 911 call center could be contacted-monitor. CDI
6.0
25.
Large container of liquid chlorine is stored in the pump room. Should be stored in the chemical storage room.
The fence has areas that has >4" between vertical members and 2" between the bottom of the fence and the ground. Due to the fence being installed prior to 2010, it is recommended to meet the current code of no more than 4" between vertical members and no more than 2" between the bottom of the fence and ground.
4.0
25.
Large container of liquid chlorine is stored in the pump room. Should be stored in the chemical storage room.
2.0
General Comments
Markings on the flow meter are fading-monitor and replace when needed.
Swimming pool ladders shall be designed to have a clearance of not more than 6" nor less than 3" between ladder and the pool wall. Pool ladder is >6"from the wall.
2.0
16.
Fencing does not meet current fencing requirements with <2"under the fence. Fence is in compliance for the year of fence construction. 2-4" under the fence. Gate is not self latching and magnetic closure and key fob reader is inoperable. gate self closes but does not self latch. 30 days to repair gate to make gate self close/self latch and repair key fob entry.
4.0
25.
A separate chemical storage area is required. large liquid chlorine barrels stored in pump room.
Swimming pool ladders shall be designed to have a clearance of not more than 6" nor less than 3" between ladder and the pool wall. Pool ladder is >6"from the wall.
2.0
16.
Fencing does not meet current fencing requirements with <2"under the fence. Fence is in compliance for the year of fence construction. 2-4" under the fence.
4.0
17.
6" of unobstructed deck spacing is required. pool furniture encroaching on deck spaces. pool furniture moved at inspection.
4.0
25.
A separate chemical storage area is required. large liquid chlorine barrels stored in pump room.
Lounge chairs are too close to the pool. There must be a minimum of 6 feet of clear walkway around pool on deck-chairs moved.CDI
4.0
23.
Automatic chlorine feeder is broken and not operational-operator is hand feeding chemicals. Intent to suspend issued to repair the automatic chlorine feeder. Do not add chemical to the pool if it is open to bathers-close then add chemical and make sure it is thoroughly mixed/dissolved and check.
The depth marker on the 5' deep section on pool deck is not attached/secured to deck. Reattach/Secure to pool deck as this could be a trip hazard.
4.0
17.
At the corner on the back right side of pool deck, the concrete is separating to different levels and the concrete patch is missing. Re-concrete so there is not a gap. Should have 6 feet of clear deck space around pool on deck
4.0
21.
Repair the lights in the female restroom.-no light currently available
4.0
23.
Motor to the chlorine feeder is not operating-repair so there is an automatic feeder on this pool.
4.0
25.
Chemicals should be stored in a separate locked storage room.
2.0
General Comments
Intent to Suspend Issued to repair #9, #17, #21, #23.
The depth marker on the 5' deep section on pool deck is not attached/secured to deck. Reattach to pool deck.
4.0
17.
At the corner on the back right side of pool deck, the concrete is separating to different levels and the concrete patch is missing. Re-concrete so there is not a gap. Should have 6 feet of clear deck space around pool on deck.
4.0
21.
Repair the lights in the female restroom.
4.0
22.
Emergency telephone is not operational-no dial tone and cannot connect to 911. Pool closed and permit suspended.
6.0
25.
Chemicals should be stored in a separate locked storage room.
Chairs must stay 6` away from pool edge. all chairs were moved to 6` away from pool edge.
4.0
25.
Fan in the pump room was not working, and there was not 2 vents in the room. Only 1 vent to outside and a nonworking fan. CPO is working on fan will come back.
2.0
General Comments
No permit is being issued. No night swimming. Pool can not open till the EO has been lifted.
pH was greater than 8.0 at start of inspection. CPO added acid and was able to lower pH to required level.
6.0
17.
Pool furniture is less than 6' from the pool obstructing pool deck. Pool furniture was moved at inspection.
4.0
25.
Liquid chlorine stored in the pump room. Chemicals should be kept separate from pump room.
2.0
General Comments
7. A few spots of remaining black algae on pool wall at 3 ft section. Algae is much improved. Continue to monitor and remove algae from pool wall. Intent lifted.
Chlorine level was reading 0 ppm at start of inspection. CPO raised to 10 ppm at inspection.
6.0
7.
Black algae spots on the pool walls and floor. clean pool walls and floor of black algae and debris.
4.0
16.
Front gate will not self latch from a short distance of opening. repair magnetic mechanism to ensure gate will self close and self latch from all distances.
4.0
17.
Pool furniture is less than 6' from pool obstructing pool deck. Move furniture to provide required walk way.
4.0
25.
Liquid chlorine stored in pump room. Chemicals should be kept separate from pump room. pump room vent fan was not on at start of inspection.
2.0
General Comments
Violatios 7,16, 17 must be corrected within 30 days. Intent to suspend issued.
The fence in the back right corner needs to be secured and have no spaces greater than 4 inches between members. Pool fence built prior to April 2010. Fix the fence.
4.0
17.
Chairs are less than 6 feet from edge of pool. CDI chair moved to create a 6ft distance of walking space around pool.
4.0
25.
Large barrel of chlorine is in equipment room. Move to the chemical room.
Chlorine was at 0 ppm. Chlorine must be at 1 ppm. CDI Chlorine added to 2 ppm.
6.0
15.
Ring buoy had deep gashes/cuts. The throw rope was too short. CDI new ring buoy was brought and rope was set to 37.5 feet long.
6.0
17.
Chairs 2-4 ft from the end of the hand rails or the edge of the pool. Must be 6ft. of clear deck space around the pool. Corrected during the inspection.
4.0
21.
The pool light has water inside the fixture and needs to be replaced.
4.0
23.
The chlorine feeder is not working properly. Needs to be replaced. Chlorine will have to be added by hand until fixed.
4.0
25.
Large barrel of chlorine is in equipment room. Move to the chemical room.
Chairs 2-4 ft from the end of the hand rails or the edge of the pool. Must be 6ft. of clear deck space around the pool. Corrected during the inspection.
4.0
General Comments
Main drain secure. Emergency telephone works. Off set of 5/8 inch in concrete has been repaired. Intent to suspend the permit has been lifted.
4 3/16 inch gap between two fence members. gap can be no greater than4 inches. Corrected during inspection.
4.0
17.
Off set in concrete near the 5 ft ladder is 5/8 inch. Offsets cannot be greater than 1/2 inch. Intent to suspend issued. Chairs within 4-5 ft of the pool edge. There must be be 6 ft. of clear deck space around the pool.
At the far right side of pool on deck, concrete pieces settled and caused >1/2" off set. Offset had previously been concreted but concrete was chipping. Operator was able to repair during inspection. There must be 6 feet of clear deck space around pool on deck. Furniture on deck is intruding.
4.0
25.
Chemicals should be stored in a separate locked storage room, not equipment room. Giant barrel of chlorine is limiting movement in the pump room and should be moved to chemical room.
2.0
29.
At start of inspection, mens toilet would not flush. Operator repaired.
There must be 6 feet of clear deck space around pool on deck. CDI chairs moved.
4.0
General Comments
In the chemical storage room and pump room, the switch to the ventilation fans was taped in the "on" position, suggest a more permanent fix. Switches must stay on to allow the vent fans to run 24 hours a day.
There must be 6 feet of clear deck space around pool on deck. Furniture is impeding on the deck space.
4.0
General Comments
In the chemical storage room and the pump room, the switch to the ventilation fans was taped in the 'on' position. Suggest a more permanent fix. Switches must stay on to allow the vent fans to run 24 hours a day.
Pool bottom is showing wear and slight pitting. If it pits to the point dirt accumulates, pool will need to be re-plastered.
On 5' end the concrete has raised some. Keep check on corner if it becomes higher than .5" then it needs to be smoothed out. It is right under .5" at this time.
0.0
24.
Flow meter is stuck, CPO is pairing during inspection.