"No Diving" markers had faded and were less than 4" in letter height. letters modified to 4" at inspection. monitor throughout the season repair as needed must be 4" in height at all times. recommend permanent repair to the letters to avoid intermittent closures due to noncompliance when the letters fade.
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
General Comments
recommend continuous forced ventilation in both pump and chemical room.
"No Diving" markers had faded and were less than 4" in letter height. letters modified to 4" at inspection. monitor throughout the season repair as needed must be 4" in height at all times.
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
General Comments
Ventilation in both chemical and pump rooms rely on cross draft ventilation. maintain cross draft ventilation. recommend to install continuous forced ventilation in both rooms. Warning no lifeguard on duty sign on gate is only warning sign in compliance. others around the pool have letters less than 4". maintain compliant sign at gate for all bathers to see upon entry. recommend adding more compliant signs inside pool enclosure.
"No Diving" markers had faded and were less than 4" in letter height. CPO arrived at pool during inspection and extended letters to 4" at inspection. "NO diving" letters must be a minimum of 4" in height.
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
General Comments
no forced ventilation in chemical room. opening to room and grates on door provide cross ventilation. maintain cross ventilation. it is recommended to add continuous forced ventilation.
one pool ladder is resting more than 6" from the pool wall. Ladders should rest 3-6" from wall.
2.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
General Comments
no forced ventilation in chemical room. opening to roof and grates on door provided cross ventilation. maintain cross ventilation. it is recommended to add continuous forced ventilation.
"No Diving" markers letter height is less than 4" and extensions had faded. Extended letters
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
"No Diving" markers letter height is less than 4" and extensions had faded. Extend letters
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
18.
Warning less than 4 inch in lettering. Extensions missing on some lettering. Repair to make lettering 4 inches.
First tested at 7.0. Operator made adjustment and now at 7.2.
6.0
9.
"No Diving" markers letter height is less than 4" and extensions had faded. Letters extended to 4" at inspection.
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
18.
Warning less than 4 inch in lettering. Operator extended lettering on sign that is on right side of pool.
"No Diving" markers letter height is less than 4" and extensions had faded. Letters extended to 4" at inspection.
4.0
16.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
Fencing is not in compliance with current fencing code. Gaps of greater than 4" in places around the fence. Fence is in compliance with fencing code of the year of its construction.
4.0
General Comments
Motor has now been inspected by building inspections dept. and approved. Permit is being issued.
Ring buoy throw rope was greater than 50' Ring buoy throw rope must be 39". Rope was shortened to correct length at inspection.
6.0
16.
Areas of the fence next to support bars have gaps slightly greater than 4" Monitor fencing and make adjustments when necessary to eliminate gaps greater than 4". Fencing is in compliance for the fencing code of the year it was built but does not meet current code of 4" or less between vertical bars.
4.0
General Comments
Motor was replaced 4/12/21 and has not been inspected by building inspections. Building inspections must sign off on electrical work before pool permit can be issued. Pool uses electronic CPO records via QR code found in chemical room. no night swimming Permit was not issued.
Ventilation must be provided in both the pump and chemical rooms. Portable mechanical ventilation used in the chemical room was able to be fixed at inspection. Repair ventilation in pump room.
2.0
General Comments
15. ring buoy rope is starting to fray. Replace with new 39' rope before the current rope dry rots. Acid feeder and cl feeders were verified to turn off when pump shuts off at inspection. Pool uses electronic CPO records via QR code.
Daily written records must be maintained. 30 days to provide records for chemical readings. Return on 8/5 to check for record book.
4.0
25.
Ventilation must be provided in both the pump and chemical rooms. Portable mechanical ventilation used in the chemical room was able to be fixed at inspection. Repair ventilation in pump room.
2.0
General Comments
15. Ring bouy rope is starting to fray. Replace with a new rope before it dry rots. 22. Emergency phone was blocked by furniture. This may be due to hurricane prep. Will return on 8/5 to check access to pool phone. Call with any questions will return on 8/5/20
Ring buoy rope around the ring had dry rotted/frayed rope. The ring buoy was replaced at inspection. Rope must be 39' and maintained in good repair.
6.0
23.
There was no form of automatic chlorination at the pool. Hand feeding of granular chlorine is not an approved chlorination method. Liquid chlorinator was removed and the new erosion chlorinator had not been installed yet. Chlorinator installed at inspection.
4.0
25.
Ventilation must be provided in both the pump and chemical rooms. Portable mechanical ventilation used in the chemical room was able to be fixed at inspection. Repair ventilation in pump room.
2.0
General Comments
Monitor fencing and landscaping to maintain 4" max under the fence at all times. Maintain 8' of deck spacing. No Night Swimming.
Pump room ventilation fan is not working. repair ventilation fan in pump room
2.0
General Comments
7. A small amount of black algae still present on the 3' side wall to the left of the stairs. The majority of the algae has been removed. 15. Flip the wing nuts over on the body hook to keep from injuring a person during rescue. 24. Monitor flow meter. The indicator inside must flow freely. repair or replace if the float gets stuck. Pool may reopen. Suspension lifted.
Free chlorine must be maintained at least 1 ppm. Pool reading is 0ppm. Repeat
6.0
7.
Black algae on the pool walls. Pool walls and floor must be clean. Remove all algae.
4.0
8.
Replace all missing weirs. All skimmers must be in good repair with weirs in place. Repeat.
4.0
10.
Replace broken floats on the safety rope.
2.0
11.
Pool Ladder is missing end caps on both feet. Replace missing end caps. Repeat
2.0
23.
Chlorine must be delivered to pool through an automatic chemical feeder. Stenner pump, pressure switch, or both are not operating. No visible chlorine in feed lines. Chlorine is being hand fed to the pool. Hand feeding is not an approved chlorine delivery method. Repair chemical pump or replace with backup erosion feeder. repeat
4.0
25.
Pump room ventilation fan is not working. repair ventilation fan in pump room
2.0
General Comments
Permit suspended. must call for reinspection prior to opening.
Chlorine level was 0 ppm at start of inspection. CPO was able to raise the Chlorine to 5 ppm at inspection.
6.0
3.
pH was reading greater than 8.0 at start of inspection. CPO was able to lower pH to 7.2 at inspection. Must remain between 7.2-7.8.
6.0
7.
Leaves throughout bottom of pool. CPO vacuumed pool during inspection to remove leaf litter.
4.0
8.
Replace all missing weirs in skimmers within 30 days of inspection.
4.0
11.
Pool ladder is missing end caps on both feet. Replace missing end caps.
2.0
23.
Chlorine must be delivered to pool through an automatic chemical feeder. Stenner pump, pressure switch, or both are not operating. No visible chlorine in feed lines. Chlorine is being hand fed to the pool. Hand feeding is not an approved chlorine delivery method. Repair chemical pump or replace with backup erosion feeder in pump room within 30 days.
There are some spots where fence meets fence posts that are greater than 4". There should be no greater than 4" of space between vertical members. Areas around the fence have greater than 2" under the bottom as per current rule. Pool is allowed to operate due to age fence was installed. Front gate was not self closing/self latching from 2" opening. Gate was repaired at inspection and will self close and self latch at all distances of opening.
4.0
25.
Pool pump room does not have mechanical or cross draft ventilation. Repair the mechanical ventilation in the pump room.
2.0
General Comments
Clean the tile at waterline where there is a build up of pollen.
At shallow end of pool, area between bottom of coping that meets pool wall is beginning to chip away. Deck is not affected at this time. Correct by next pool season.
0.0
16.
There are some spots where fence meets fence posts that are greater than 4". There should be no greater than 4" of space between vertical members. Pool is allowed to operate due to age fence was installed.
Some depth markers/no diving are beginning to fade, repaint as needed throughout the year so they are easy to read.. At this time they are dark enough.
0.0
16.
Entrance gate had diagonal cable for support. This cable was removed. There can be no footholds to climb gate.
Rope on the ring buoy was 39 feet long-however the way it was attached to the ring buoy was wrong. Rope was doubled up and tied at end making it only 19 1/2 FT long. repaired during the inspection.
6.0
25.
The light in the equipment room was unable to be turned on - repair.
Mechanical fan in the equipment room is wired to the light switch. Switch was taped in the on position. Mechanical fan in the chemical room is not operating. A portable mechanical HVAC unit with outside air intake is in the room. This unit must stay on and cut out in door must stay unblocked.
Many of the depth markings on the pool deck have faded and need repainting. Repaint all depth markings and faded NO DIVING markings on pool deck by August 18th, 2012-Intent Issued.
4.0
25.
Lights in the pump room are not operating-Repair.
2.0
29.
Hot water in the restrooms was ~113F (maximum of 110F).
There are several cracks in pool walls and missing tiles around skimmers. These are several spots at cracks where there is expose metal. there are several spots where coping is cracked or missing. these must be repaired by next season or permit will not be issued.
4.0
15.
Ring buoy is in poor repair and not usable. Was replaced by end of inspection!