Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 06/02/2023
Score: 26
#
Comments
Points
3.
Pool pH upon arrival was 8ppm. pH shall be 7.2-7.8 and maintained. CDI Operator was able to lower pH to 7.4.
6.0
11.
Steps on the ladders are over 6' from the pool wall. Should be between 3' and 6' from the pool wall.
2.0
12.
Inlets were missing eyelets and 2 were missing whole unit. Inlets should be in good repair.
4.0
17.
Pool should have 6 feet of walkway around pool on deck- fence too close on backside of pool and interfering with the 6' requirement.
4.0
19.
Pool rules sign letters shall be at least 1" stating correct verbiage as per .2530 (c). CDI Operator added new sign in compliance.
4.0
24.
Filter should have a pressure gauge and relief valve.
4.0
25.
Chemicals should have a separate storage room.
2.0
29.
Hot water in restrooms is >110F. Should not be any warmer then 110F.
0.0
General Comments
Vac-less SVRS was checked and is proven to be operable. Keep daily written records of pH, free chlorine and main drain checks. Keep weekly written records of total alkalinity and cyanuric acid.
911 call center has old address of Industrial Park Dr., need to update to Outlet Center Dr. Operator should monitor ring buoy, showing signs of aging.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 05/17/2022
Score: 14
#
Comments
Points
11.
Steps on the ladders are over 6" from the pool wall. Should be between 3" and 6" from the pool wall.
2.0
17.
Pool should have 6 feet of walkway around pool on deck- fence too close on backside of pool and interfering with the 6' requirement.
4.0
24.
Filter should have a pressure gauge and relief valve.
4.0
25.
Chemicals should have a separate storage room. Currently stored in pump room that does have mechanical ventilation and light. Make sure fan stays on at all times.
2.0
29.
Hot water in restrooms is >100F. Should not be any warmer then 110F.
2.0
General Comments
Vac-less SVRS was checked and is proven to be operational.
FLow ~60GPM
-Keep daily written records of pH, free chlorine and main drain checks. -Keep weekly written records of total alkalinity and cyanuric acid levels. -No Lifeguard sign by parking lot is approved. -911 call center has the old address of "Industrial Park Dr.", update with them to "Outlet Center Dr."
Pool constructed prior to 1990, all listed violations should be repaired but not required due to age.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 05/24/2021
Score: 10
#
Comments
Points
11.
Ladders installed over 6" away from pool wall. Ladder should be installed at a distance of 3" to 6" away from pool wall.
2.0
17.
There should be 6' of clear walkway around the pool deck. Fence placement on the deep end is closer then 6' to the pool.
4.0
25.
Should have separate room for chemical storage other then pump room.
2.0
29.
Hot water in the restrooms is >110F, currently ~115F. Should not be any warmer then 110F.
2.0
General Comments
*Keep daily records of pH, free chlorine and main drain checks. *Keep weekly cyanuric acid levels and total alkalinity *The "WARNING NO LIFEGUARD ON DUTY" sign by the road/parking lot is compliant, 1 by hotel is not.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 07/31/2019
Score: 26
#
Comments
Points
3.
pH at start of inspection was a 8.0 or higher. Operator was able to adjust and now a 7.2. Monitor to make sure it stays in the rang of 7.2-7.8. CDI
6.0
5.
Make sure the total alkalinity and the cyanuric acid levels are checked and recorded weekly.
0.0
6.
The first time the vac-less system was tested, it did not work. System was reset and proven to be operational. Monitor and test system daily to make sure it is properly operating. Pool must close if not operating properly.
6.0
11.
Ladder should be installed at a distance of 3inches to 6inches away from pool wall - it is currently over 6 inches.
2.0
15.
At start of inspection, the ring buoy had several tears exposing the inside foam- this unit is in bad repair and not approved. Operator was able to immediately replace with a new ring buoy. Always provide a ring buoy that is in good repair. Ring buoy that was in bad repair was removed from the pool deck.
6.0
17.
There should be 6' of clear walkway around the pool deck. Fence placement on the deep end is closer then 6' to the pool.
4.0
25.
Chemicals should be stored in a separate locked chemical storage room away from the pump room. Fan to the pump and chemical storage room has a switch on the wall that is accessible. Switch should be made inaccessible with a cover.
2.0
General Comments
Due to the age of the pool (before 1991) #11, #16 and #25 should be compliant but not mandated. If it suggested to repair all items.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 05/09/2019
Score: 18
#
Comments
Points
6.
At the start of inspection, the Vacless SVRS was not operational- System was removed and reinstalled. Vac-less SVRS was repaired and proven to be operational.
6.0
11.
Ladder should be installed at a distance of 3" to 6" away from pool wall, currently over 6".
2.0
17.
There should be 6' of clear walkway around the pool deck. Fence placement on the deep end is closer then 6' to the pool.
4.0
24.
The pressure relief vale on filter is not operational- replace.
4.0
25.
Should have separate room for chemicals other than pump room. Make sure the fan in equipment room stays on at all times.
2.0
General Comments
Rope on ring buoy is 27 feet.
Record daily pH, free chlorine and main drain checks. Weekly total alkalinity.
The WARNING NO LIFEGUARD sign by road is compliant -all others are not.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 07/25/2017
Score: 18
#
Comments
Points
3.
pH of pool water was >8.0 at start of inspection. pH decreaser was added and now pH is 7.8. Monitor and make sure it stays between 7.2-7.8.
6.0
15.
Ring buoy was in bad repair and throw rope was knotted up. Ring buoy replaced with new one and a 28 foot rope was attached. Do not remove the approved ring buoy and place damaged buoy on pool deck. Must have approved safety equipment at all times.
6.0
17.
There should be 6 ft. of clear walkway around the pool deck. Fence placement on the deep end is closer than 6 ft. to the pool.
4.0
25.
Should have a separate chemical storage room. Make sure the fan in equipment room stays on at all times.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 07/28/2015
Score: 6
#
Comments
Points
17.
There should be 6 ft. of clear walkway around the pool deck. Fence placement on the deep end is closer than 6 ft. to the pool.
4.0
25.
Some chemicals are stored in the pump room. They should be stored in a separate room with lighting and proper ventilation.
2.0
General Comments
Records were available for todays inspection. Need to record a daily check of the main drain cover instead of weekly. Weekly recording of total alkalinity and cyanuric acid levels must be included in the records. Stingl switch was shown to be operating properly. Emergency telephone works.
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 04/30/2012
Score: 18
#
Comments
Points
2.
Chlorine level at start of inspection was less than 0.5ppm. Pool water must have a free chlorine level of 1.0ppm at all times (1.0ppm minimum).
6.0
3.
pH at start of inspection was >8.0. pH of pool water must stay between 7.2 - 7.8 at all times.
6.0
11.
Ladder steps should be between 3" and 6" from pool wall.
2.0
17.
Must have 6 feet of clear walkway around pool on deck. (fence obstructs the 6' space).
4.0
18.
WARNING NO LIFEGUARD ON DUTY SIGN is compliant on far side of pool (on fence b/l trees) Must keep this sign posted as the other sign is not 4" and not compliant.
0.0
General Comments
***Stingyl vacuum release system is properly operating***
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 05/12/2011
Score: 16
#
Comments
Points
8.
Equalizer lines were blocked in skimmer basket-plugs were removed. Keep unblocked, approved VGB covers installed.
4.0
11.
Ladder steps should be between 3" and 6" from pool wall.
2.0
17.
Must have 6 feet of clear walkway around pool on deck.
4.0
18.
No lifeguard warning sign was not compliant (<4 letters). Sign was replaced. "WARNING NO LIFEGUARD ON DUTY" IN 4" TALL LETTERS MINIMUM.
4.0
25.
Vent fan was off at start of inspection - tape switch so it stays on at all times. Chemicals should have their own approved chemical storage room.
2.0
General Comments
-DO not place chlorine sticks in pool water. -Fence is new construction 2011-approved -***Stingyl vacuum release system is properly operating-skimmer valve removed and in the on position***
Location: 1705 Outlet Center Dr. SELMA, NC 27576 Facility Type: Seasonal Swimming Pools Inspection Date: 04/30/2010
Score: 14
#
Comments
Points
1.
Water slightly cloudy-able to see drains clearly. Monitor to make sure water clarity stays or improves.
0.0
8.
Equalizer lines have been capped in the skimmer to eliminate a suction hazard. Must have VGB compliant covers/grates and unblock by 2011 operating season.
4.0
11.
Ladder steps should be between 3" and 6" from pool wall.
2.0
16.
Gate should open away from pool. There should not be more than 4 inches between the vertical members on fence and gate. Both items must be repaired by 2011 operating season.
4.0
17.
Must have 6 feet of clear walkway around pool on deck.
4.0
25.
Tape the switch on to the ventilation system in pump/chemical room. Cannot be turned off.
0.0
General Comments
Letter from BAI architects received and approved stating compliance with VGB Act. -Stingl vacuum release system proven to be properly operating. -Skimmer valve removed i pmp room-open