Vacuum cover should be self closing, self latching. Vacuum cover was broken so it is no longer self latching. Operator will replace. Operator ordered new cover during inspection. Expected arrival is tomorrow.
4.0
17.
There should be a minimum of 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladder handrails interfere with the clearance.
4.0
29.
Hot water in the restrooms should be a maximum of 110F. Hot water was 120F plus.
There should be a minimum of 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladder handrails interfere with the clearance.
4.0
29.
Hot water in the restrooms is >120F. Should be a maximum of 110F.
There should be a minimum of 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladder handrails interfere with the clearance.
4.0
29.
Hot water in the restrooms is >120F. Should be a maximum of 110F.
2.0
General Comments
Skimmer lids are screwed down and new floor recently poured which did not allow for the guard on duty to be able to remove. Pool subject to inspection and permitting at the end of the month-all skimmer lids must be removed/removable at that time. Make sure all skimmers have weirs and that the equalizer line is plugged since it is plugged on pool wall.
There should be a minimum of 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladder handrails interfere with the clearance.
4.0
29.
Hot water in the restrooms is >110F. Should be a maximum of 110F.
There should be 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladders/handrails interfere with the clearance.
4.0
29.
Hot water in the restrooms was 124F. Should not be any warmer then 110F.
There should be 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladders interfere with the clearance.
4.0
29.
Hot water in the restrooms was 118F. Should not be any warmer then 110F.
There should be 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladders interfere with the clearance.
4.0
29.
Hot water in the restrooms was 118F. Should not be any warmer then 110F.
Ring buoy on pool deck had a tear in it exposing the inside material. This buoy is in bad repair and cannot be used. Lifeguard w/ rescue tube must stay on duty while pool is open to bathers until a new buoy can be provided. CDI
6.0
17.
There should be 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladders interfere with the clearance.
4.0
29.
Hot water in the restrooms was 124F. Should not be any warmer then 110F.
Rope on the provided ring buoy was short. Due to the size of the pool, the rope must be 50 feet long. Ring buoy and rope was switched with the ring buoy and rope on smaller therapy pool. Rope was 50 feet long -repaired.
6.0
17.
There must be 5 feet of clear walkway around pool ladders on deck. There is currently only 5 feet of walkway total and the ladders interfere with the clearance.
4.0
29.
Hot water in the restrooms was 122F. Should not be any warmer than 110F.
Screw was loose on one of the equalizers - repaired. Make sure they stay secure at all times.
0.0
12.
One inlet missing internal adjuster portion - repaired.
0.0
13.
The contrasting color band on steps must be no more than 1 inch back from edge.
4.0
17.
Should have 5 feet of clear walkway around pool on deck.
4.0
23.
The automatic acid feeders continued to pump when the circulation system is off. The feeders should turn off automatically when pump system is off. Ecolab on site are repaired during the inspection.
4.0
29.
Hot water at restroom sinks was 121F. Cannot be warmer than 110F.
Should have 5 feet of clear deck space around all handrails.
4.0
23.
The automatic acid feeders continued to pump when the circulation system is off. The feeders should turn off automatically when pump system is off. System repaired-now shutting off.
4.0
25.
Water is leaking from a seal below pump on to the floor. Pump and all electrical sit up above floor. Repair leak.
2.0
29.
Hot water at sinks in restroom was 130F. Should not be warmer than 110F.
Equalizer lines for surface skimmers have been plugged. VGB compliant covers must be installed in the wall under the skimmer and plugs in skimmers must be removed by April 1, 2011.
4.0
13.
Colorband on steps should not be greater than 1 inch away from pool edge.
4.0
17.
Must have 5 feet of clear walkway around pool deck.
4.0
29.
Maximum water temp. in bathroom should be 110F.
2.0
General Comments
-Check with 911 operator to make sure contact number is correct. -Will return on April 1, 2011 to verify copliance with equalizer covers in surface skimmers.