Floor inlet by basketball goal is broken. Must be replaced with one that is in good repair.
4.0
15.
Both lifeguards were not on duty and in office, no ring buoys on pool deck. Pool must have 2 lifeguards on duty -or- 2 ring buoys with rope at all times pool is open to ppl on deck. Lifeguards are now on duty at all times.
6.0
18.
Lifeguards not on duty and there is not a "WARNING NO LIFEGUARD ON DUTY" sign. Provide one in 4" minimum lettering.
4.0
General Comments
Emergency phone is operational but no sign by it-manager making with dialing instructions, pool address and phone number. CDI
Repair damaged/broken inlet by 8-23-24 and Lifeguards must stay on duty at all times.
Only 1 lifeguard on duty at time of inspection. Pool requires two sets of lifesaving equip at all times. Ring buoy rope had dry rotted and in poor repair. Replaced ring buoy with a spare in good repair at inspection. Monitor ring buoy throw rope and rope around buoy for decay and fraying
6.0
23.
Chlorine tablets found in all skimmers. "Skimmer sticks" must be used in NSF chlorinator and not placed in pool directly. Skimmer sticks in the skimmer is not an approved chlorination method. sticks removed at inspection.
Main drain on the right is missing a screw. All screws to main drain must be install to manufactures requirement. Lifeguard cound not get screw into main drain. Make sure all screws are in place and secured.
6.0
24.
Flow meter is stuck, must be free flowing while pump is on.
Ladder at 4' end needs and end cap and is loose. Ladder in diving section on right (pump building) is also loose.
2.0
15.
Two ring buoys are out on deck. Once ring buoy rope is worn and can not be on the deck. CPO took out. If lifeguards are on duty then ring buoys are not required. If there is adult swim during lifeguard break then: A sign 4" tall stating "Warning no lifeguard on duty" must be posted. AND two ring buoys with 50' long ropes in good repair must be out along with the 2 body-hooks.
6.0
General Comments
Permit is being issued and night swimming is allowed.
Chlorine was 0ppm at the beginning of inspection was at 1 ppm when last checked.
6.0
8.
This skimmers do not have equalizer lines.
4.0
9.
do not cover up any depth or no diving markers with play equipment. Some depth markers and no diving markers were faded. Jamie recolored during inspection.
4.0
25.
Light is needed in chemical storage building. All chemicals must be stored in separate area from pump room.
General comments: Daily record for main drain covers are needed on a daily basis.
0.0
7.
Pool walls have algea in the diving area. Clean pool walls so algea is not present.
4.0
8.
Skimmers do not have equalizer lines. Weir is missing in skimmers beside taller diving board. Clean skimmer baskets out.
4.0
13.
Contrasting color band is fading and chipping. Will not to be repainted. (On entry steps).
4.0
16.
Gate is not self-latching or self-closing and there was no gate attandant. Repair gate or have attandent present. Service gate was open along with side gates to playground. All gates from outside pool fence must be locked. Manager closed service gate.
4.0
17.
Deck should have 8feet of clear walking space around pool. 3ft side has chairs located within 8 ft of pool deck.
4.0
18.
General comments: 2nd lifeguard needs a rescue tube. No telescopic pole for hook (2nd pole).
0.0
24.
Flow meter is stuck. Repair flow meter so that it is working properly.