The free chlorine level in the pool is not measurable. Must have a minimum of 1ppm. Operator was unable to increase levels-Pool Permit Suspended
6.0
7.
Dark areas of fungal growth on pool floors and walls-clean to remove.
4.0
15.
Ring buoy was not US Coast Guard approved and rope was too short. Operator replaced with a US COast Guard buoy with a 50' rope. CDI
6.0
16.
Several areas of the fence have more then 2" between the ground and bottom of fence-repair.
4.0
24.
Flow meter not operating-repair
4.0
General Comments
Ground wire to the feature motor is not connected-Electrician must reattach and Building Inspections must inspect. Contact them for a permit prior to doing so.
Pool Permit Suspended until #2 corrected and Building Inspections inspects and approves.
Several surface skimmers were missing weirs. Weirs must be in place for proper operation. Operator was able to replace all missing weirs. CDI
4.0
16.
On the back right side of the pool deck, there are areas that have more then 2" between the pool fence and ground. Should not have more than 2" between the ground and bottom of fence. Operator was able to repair by providing mulch. CDI
4.0
General Comments
Feature main drain covers, circulation main drain covers and equalizer line covers expire 4-8-2024. All must be replaced with covers that are approved for the flow and sump by 4/8/24 and a new drain data sheet submitted. Permit will be suspended if not completed.