The circulation system is not running which means there is no filtration of pool water and no disinfectant provided. Pool closed until circulation system is operating and it is reinspected.
6.0
9.
4ft depth markers were less than 4". Depth markers shall be at least 4". operator fixed to meet the 4" requirement.
4.0
11.
Treads on pool ladders are missing making steps not slip resistant
2.0
12.
inlet covers are missing
4.0
17.
Chairs are too close to pool edge. Must have 8' of clear walkway around pool on deck.
4.0
General Comments
Unable to inspect equipment room items due to the circulation system not operating. Permit immediately suspended. Pool closed sign posted and occupants of pool notified of closure and left pool deck.
Can open when circulation system is operating and a reinspection is done. clean leaves from storm debris
One area in fence has vertical gap bigger then 4 inches. In compliance for year of construction.
4.0
General Comments
closely monitor pH. pH was at 7.8 with cat controller reading 8.0. The stenner for the acid was not operating during inspection. pH must remain between 7.2-7.8. Replace any missing inlet covers on returns. Correct phone # for 911 phone is 919 351-9520. update sign at phone.
CPO must keep daily written records onsite so they can be reviewed.
4.0
12.
2 inlets are missing in deep end of pool, replace.
4.0
15.
Both ring buoys were in poor repair and rope that is permanently attached to buoy is fraying apart. Two new ring buoys were installed at opening inspection, these do not appear to be the new ones from 4 months ago. Replace
The both ring bouys were worn, CPO replaced with new ring bouys.
6.0
17.
The plastic zipper flillers in the concrete are breaking. One area was filled-in. If plastic continues to break then a permanent fixture will be required.
0.0
18.
The "Warning No Lifeguard on Duty" sign had lettering not 4" tall. CPO used material to get lettering 4" tall.
Phone has two different numbers that go through the phone. Changed sign to phone number 911 had. Check to make sure that continues to be the correct number. No night swimming. Can not open until executive order has been lifted.
Gate to pool would not close and latch properly. Spring was worn and stretched and bottom of gate was scrubbing ground. Gate was repaired by end of inspection with bungee cord, but it is still scrubbing and not closing properly.
Floats on the safety rope are greater then 5 feet apart. Add additional floats so that there is not more then 5 feet between any float and float to pool wall.
2.0
12.
One inlet on pool wall in the 8 foot deep end is missing the cover plate and eye-Repair by 8-17-17.
4.0
15.
Rope on both of the ring buoys was knotted up and wrapped around buoy-making it difficult to access. I fixed during inspection.
6.0
General Comments
Repair violation #12 by 8-17-17 in order to remain in operation.
Pool plaster is getting worse. Plaster is in bad repair in a lot of areas. Repair damaged areas so that these areas do not cause issues with pool. Repair by next pool season opening!
4.0
12.
Couple inlet fittings were missing. Replaced before end of inspection.
4.0
24.
Flow meter was stuck. Repaired before end of inspection.
2 skimmers have been blocked at the 11/2ft left side and between 6 & 5ft right side. They are blocked for structual reasons. Once skimmer did not have a weir, it was replaced during inspection.
4.0
11.
Two ladders are missing end caps, replace missing end caps to ladders.
2.0
15.
Ring buoy was in bad repair, it was replaced during inspection.
6.0
17.
There was some trip hazards that was repaired during inspection.
4.0
General Comments
Lock Box: 1968, Permit is being issued. Open from dawn to dusk.
Skimmers have trash and leaves inside, dump all trash and debris out of skimmers.
4.0
12.
Light fixture in pool is popped out of pool wall. Underwater light niches shall be maintained so not to present a potential hazard. Fix light fixture. Pool is closed!!!